Tech specs
Type4 ManualCallPoint Jeweller
Wireless Type 4 addressable resettable button for manual fire alarm activation

Device compatibility
CheckDevice compatibility
Communication
Jeweller communication technology
Proprietary wireless communication technology to transmit commands, alarms, and events.
Key features:
- Two-way communication.
- Advanced sabotage protection.
- Block encryption featuring a dynamic key.
- Instant notifications.
- Remote control and configuration in Ajax apps.
Frequency bands
868.0–868.6 MHz
Depends on the sales region.
Maximum effective radiated power (ERP)
up to 25 mW
Automatic power control to reduce power consumption and radio interference.
Radio signal modulation
GFSK
Radio communication range
up to 1,700 m
Between the device and a fire alarm central unit or a range extender in an open space.
Encrypted communication
All stored and transmitted data is protected by block encryption featuring a dynamic key.
Frequency hopping
To prevent radio interference and jamming.
Key features
Resettable frangible element
activates the button
When the central part (frangible element) is pressed, the button depresses inward, triggering an alarm or initiating a scenario. Two yellow stripes appear at the top and bottom, indicating the device's state.
Operating modes
- fire alarm
- evacuation
- auxiliary alarm
- fault alert
- panic button
- gas leak alarm
- water leak alarm
- custom action
With appropriate settings, it activates an alarm or controls Ajax automation devices.
LED status indication
fire alarm
faults
The LED indicator on the device enclosure lights up when a fire alarm is triggered or faults are detected.
Interconnected fire detector alarms
by pressing the button
By pressing the frangible element, fire detectors in the system trigger the built-in sirens.
Critical alerts
The system can activate intrusion sirens and send audible alarm notifications to users, even if the sound is muted, the Do Not Disturb mode is on, or headphones are connected.
Protection against accidental presses
Lift the transparent lid to access the frangible element. The lid protects against false button presses.
Alarm transmission to CMS
can be disabled

Special tool (key)
Button reset
after pressing
To reset the button, insert the special tool into the corresponding hole.
Hole in the enclosure
to hang on a ring from a keychain
The person responsible for fire safety can carry the special tool on their keychain.
Convenient dismantling
The special tool opens the lock to dismantle the device from SmartBracket mounting panel.


Installation recommendations
It is recommended to install the button in easily accessible places at a height of 1.4 m.
The device is designed for outdoor and indoor use.
Sabotage protection
Tamper button
Notifies on attempts to detach the button from the surface or remove it from the mounting panel.
Protection against spoofing
device authentication
Connection loss detection
after 36 s
Detection time depends on Jeweller settings.
Power supply
Battery
2 × CR123A
Pre-installed. With typical use (one press lasting 1 minute per week), the batteries can last up to 7 years.
Enclosure
Dimensions
102 × 104 × 39 mm
Weight
214 g
Operating temperature range
from 0 °C to +50 °C
Operating humidity
up to 80%


Color
Red

Complete set
Type4 ManualCallPoint Jeweller
SmartBracket mounting panel
Special tool (key)
2 × CR123A battery (pre-installed)
Installation kit
Quick start guide
Revision