Wireless Type 4 addressable fire alarm central unit

Device compatibility
Capacity
Wireless Ajax devices
up to 100
Supports only Ajax devices from the Type4 product line in any combination, except for a single Type4 Fire ReX Jeweller range extender.
Users
up to 50
- Any number of admin users within the fire alarm central unit limit.
- PRO accounts for installers.
- PRO accounts for installation and monitoring companies.
- Access management for users.
Automation scenarios
up to 5
- By alarm.
- By schedule.
- By arming/disarming.
Security groups
up to 9
Rooms
up to 50
Wireless communication
Jeweller communication technology
Proprietary wireless communication technology to transmit commands, alarms, and events.
Key features:
- Two-way communication.
- Advanced anti-sabotage.
- Block encryption featuring a dynamic key.
- Instant notifications.
- Remote configuration via the Ajax apps.
Radio frequency bands
868.0–868.6 MHz
Maximum effective radiated power (ERP)
up to 25 mW
Automatic power control to reduce power consumption and radio interference.
Radio signal modulation
GFSK
Radio communication range
up to 2,000 m
Between the fire alarm central unit and connected devices (in an open space).
Maximum range depends on the connected device.
Polling interval
from 12 to 300 s
Adjusted by PRO or user with admin rights in the Ajax apps.
Encrypted radio communication
All the data stored and transmitted is protected by block encryption featuring a dynamic key.
Frequency hopping
To prevent radio interference and jamming.
Communication channels
Ethernet
1 8P8C socket
Up to 100 Mbps.
Cellular
1 micro-SIM slot
Cellular bands
4G (LTE)
GSM 850/900/1800/1900 MHz
Automatic switching between communication channels
Instant switching between Ethernet and SIM.
Communication channels prioritization
- Ethernet
- Cellular connection
Communication channels work in parallel, to increase system reliability. Most of the data is transmitted via Ethernet.


Notifications
Supported notification types
- Push notifications
- SMS
Event types
- Alarms
- Faults
- Security state change
- System events
- Non-security alerts
The notification types are configured individually for each user.

Monitoring
Supported protocols
- SIA (DC-09)
- SurGard (Contact ID)
- ADEMCO 685
- Other proprietary protocols
Event types
- System alarms and events
- Panic button coordinates
Installation recommendations
Type4 Hub (4G) Jeweller is designed for indoor installation only.
The device operating voltage is 110–240 V~.
Sabotage protection
Tamper button
Notifications about the fault on attempts to detach the device from the surface or remove the mounting panel.
Protection against spoofing
device authentication
Connection loss detection
after 36 s
Detection time depends on Jeweller settings.
Power supply
Main
110–240 V~, 50/60 Hz
Up to 10 W of mains power consumption.
Backup
built-in backup rechargeable battery: Li-ion 3 А·h
Up to 15 hours of offline operation when the Ethernet is switched off.
Type4 Hub (4G) Jeweller has a 3-pin battery. To replace the battery, use the same one.
Alternative
6 V⎓ (when using 6V PSU (type A))
12–24 V⎓ (when using 12–24V PSU (type A))
Requires the appropriate alternative power supply unit (sold separately).
Enclosure
Dimensions
163 × 163 × 36 mm
Weight
361 g
Operating temperature range
from −10 °C to +40 °C
Operating humidity
up to 75% non-condensing
Protection class
IP20

Color
Red

Complete set
Type4 Hub (4G) Jeweller
SmartBracket mounting panel
Power supply cable
Ethernet cable
Installation kit
GSM start package (available not in all countries)
Quick start guide
Revision
1
Ćēŕţĩƒĩćàţĩōń àńď ćōḿƥĺĩàńćē ŵĩţĥ śţàńďàŕďś

Type4 Hub (4G) Jeweller